ATTENTION !
Default port of Industrial Automation (Modbus Gateway) service is 502.
If on the local network is conflict with other network service using the same port, in the converter's port configuration
change number of port into another for the server and client service.
On section Advanced Protocol Settings (fig. below), set the time out by entry:
Character timeout - value in ms., maximum delay or gap betweens bytes of a message – default 20 ms.
Message timeout - value in ms., maximum delay or gap betweens bytes of a message default 2500ms; this time not must be
less than the timeout set on MODBUS MASTER devices / SCADA/HMI software.
For saving the Advanced Protocol Settings press [Apply].
Fig. 30. Example configuration for communication with MODBUS-SLAVE devices – configuration of timeout parameters for
SLAVE type device
5.3.2.1.5.3. SERIAL PORT TRANSMISSION PARAMETERS
For proper operation of ADA-13040MG with devices Modbus-Master or Modbus-Slave types, connected to his RS485/RS422 serial
port, should be set the same transmission parameters for both devices.
Select Basic Serial Settings and enter Baud Rate, Data Bits, Parity, Stop Bits, the same parameter like has device connected to
the serial port of the converter.
5.3.3. SYSTEM SETTINGS
Select on left panel menu Configuration -> System and then on right will be selections as follow:
Device Identity Settingsallows to add name of converter, describe the location and add identification number,
Simple Network Management Protocol Settings (SNMP) – allows to make the configuration of management protocol SNMP.
5.3.4. USERS CONFIGURATION
On the configuration page Users are two sections:
Users
Configure Users
The section Users allows to configure the method of login to ADA-13040MG. Selecting the option Enable user logins means that
after enter the address http://<adres-ip-konwertera>/admin/administration.htm to internet browser, will open login window and will be
necessary to enter user name and password.
The section Configure Users allows to add additional user, change password, configure access and permissions for each defined
users.
5.3.4.1. CHANGING USER MANE AND PASSWORD
Changing the default user root and password, can be done as follow :
1. press user mane root in section Users Configuration->Configure Users,
2. enter new user name and password.
3. press [Apply] for saving.
5.3.4.2. ADDING NEW USER WITH LIMITED PERMISSIONS FOR CONFIGURATION OR
MANAGEMENT
For adding new user with limited permissions for configuration or management follow the steps below:
1.From menu Configuration select Users,
2. In section Configure Users, press [New...],
3. Enter user mane (eg. admin) and password – twice, and press [Apply],
4. Will open the page Users Configuration, where in section Configure Users, will be new user name.
Now it is possible to configure access permissions to the converter and permissions for configuration of this new user.
Configuration of access to converter:
1.From menu Configuration select Users,
2. In section Configure Users, select added user eg. admin,
3. Will open the page User Configuration – admin, where are sections:
A/ User Configuration – possibility of rename user and password,
B/ User Access - method of access to converter from the network:
Allow command line access – access using the Command Line Interface - telnet,
Allow web interface access – access using the internet browser.
23
ADA-13040MG