Fig. 25. Example configuration for communication with MODBUS-MASTER devices – table entry configuration for SLAVE type
devices
On section Advanced Protocol Settings (fig. below), set the time out by entry:
Character timeout - value in ms., maximum delay or gap betweens bytes of a message – default 20 ms.
Message timeout - value in ms., maximum delay or gap betweens bytes of a message default 2500ms; this time must be less
than the Timeout set on SLAVE and MASTER MODBUS-RTU devices.
For saving the Advanced Protocol Settings press [Apply].
Fig. 26. Example configuration for communication with MODBUS-MASTER devices – configuration of timeout parameters for
MASTER type device
5.3.2.1.5.2. CONFIGURATION FOR COMMUNICATION WITH MODBUS-SLAVE TYPE
DEVICE
In section Industrial Automation Settings, press [Change Protocol] link. Then in section Select IA Protocol (figure below) select
type of device, connected to serial port of ADA-13040MG as Serial Slave and MODBUS-RTU or MODBUS-ASCII protocol for
communication between connected devices. Press [Apply] for saving configuration.
21
ADA-13040MG