Fig. 22. Example configuration for communication with MODBUS-MASTER devices – choice of devices and protocols
Set the options in section Modbus RTU Settings like on the figure below and press [Apply].
Fig. 23. Example configuration for communication with MODBUS-MASTER devices – Modbus RTU setting
Then select section Slave Destinations (Packet Routing)figure below.
In this section press [Add], enter the IP address of Slave type devices, to which Master will send requests and receive responses.
Fig. 24. Example configuration for communication with MODBUS-MASTER devices – table configuration of SLAVE type
devices
In section Destination Settings (fig. below) set the options of requests from Master device to Slave device, in fields:
Host name - enter IP address of Slave device.
Protocol - set protocol which will be send to Slave device – in this case will be Modbus/TCP.
Transport - set TCP protocol .
Network port- set port 502.
Press [Apply] for saving configuration. Then press again [Add] for adding another Slave device.
Then select section Slave Destinations (Packet Routing), when all Slave devices are added and set, press [Apply].
20
ADA-13040MG
Vista de página 19
1 2 ... 15 16 17 18 19 20 21 22 23 24 25 26 27 28